Vapor Control Automatic Shutdown Log


Old Vapor Control System Automatic Shutdown Log

Shutdown Date Description
02/27/11 Shutdown from 1445 to 1500, Liquid Seal Level Low.
06/16/11 Prior to loading, electricity changed started on crane breaker.
06/26/11 At 1145, High Stack Temp./Flare Failure Shutdown.
1205 High Stack Again.
Closed Flare Valve down to 50%.
07/21/11 2350: High Liquid Seal Level.
08/05/11 Back to Back ESD’s; High Stack Temp at Flare.
Barge FMT 3084
09/17/11 0900 Down.  Vessel Overfill Hignh O2 Alarm.
Alarm Pulled and Reset.
0950 Restarted.
1350 Down Again; Vessel Overfill Alarm Pulled.
1355 Restart and Reset Alarms.
11/30/11 High O2 Shutdown.
02/04/12 1305 – 1355 Bad Weather. High Level Alarm, Flare Pilot Failure shut me down.
04/11/12 0405 – 0419 Low Seal Flare Failure (liquid level).
05/03/12 1620 High O2 Shutdown / Fuel Gas valve went to 0% while in auto / unknown cause / restart at 1630.
05/08/12 0835 Low level seal pot shutdown.
05/25/12 1340-1405 High level liquid seal shutdown.
05/25/12 1635-1650 High level liquid seal shutdown.
07/23/12 1920-2020 Loading Pump Shutdown.
10/17/12 0700 BM & SB calibration on O2 & H2O pressure sensors.
0820 Start Loading Kirby barge T-Bone transfer “25,000 bbls”.
1030 George checked H2O pressure on vapor line found no bad readings.
1035 O2-12.40% / 45.2% FG / H2O psi 16.7 @ 2,423 bbls per hour.
1135 raised bph from 2345 – 2588 / O2-12.44% / 45.5 FG, H2O psi 16.1 – Filled fuel pot @ flare 1/4 till low level.
1230 raised bph from 2360 bph – 2647 bph. No answer to how or why the rate went down.
1240 bph 2584 O2-12.14% psi 17.0.
1440 Flow rate 100% 2850 bbls/hr.
1500 bbls/hr 2834 O2-12.47% / H2O psi 14.7.
03/01/13 0130-0310 Tried to find out why there was no flow. Tankerman did not have valves fully open. 0420-0445 Air Compressore quit working and clsosed all control valves. After fiving it a rest, we resumed. 0520 Shutdown no air pressure. 0750 Restart. After ESD panel repair. 0810 Down. Fuel Gas Valve Bad – Broken. 1120 Restart after repair. 1435-1520 Shutdown to refuel compressor.
05/15/13 0530-0600 Shutdown due to Low Liquid Level at Flare.
05/21/13 1415-1540 Shutdown while swapping from Tebone to Crosstex.
08/06/13 1140-1158 Shutdown due to High Seal Pot Level. Did not resume loading Barge K29014 until 1239 so pressure could be flared from vessel.
09/04/13 0725-0738 High pressure shutdown.
09/07/13 0751-0801 High Pressure Shutdown.
09/12/13 1930-1945 Flare shutdown. Liquid Seal Pot. Drained enough to get alarm to clear and restarted loading.

New Vapor Control System Automatic Shutdown Log                                          PDF

Date Time Product Reason for Shutdown Remedial Actions
10/10/14 0100 Natural Gasoline Burner 4 High High Temp. Re-started Flare and resumed loading
10/10/14 1724 Natural Gasoline Burner 4 High High Temp. Re-started Flare and resumed loading
10/10/14 1750 Natural Gasoline Burner 4 High High Temp. Flare Gas still running. Showed off at panel. Re-started Flare and resumed loading
10/11/14 0100 Natural Gasoline Low Flow to O2 Analyzer Restarted
10/11/14 0114 Natural Gasoline Low Flow of A O2 Analyzer Restart left fuel gas valve in manual at 10%. It was at 0%.
10/11/14 1200 Natural Gasoline Low flow to A O2. Adjust floating ball in cabinet
10/11/14 1300 Natural Gasoline FC 1201 Spare Swapped fuse
10/18/14 0930 Natural Gasoline High burner temp Established vapor flow
10/18/14 1220 Natural Gasoline High High O2 Lowered flow rate
10/18/14 1550 Natural Gasoline High burner temp / Bad thermo Called to fix thermo weld
10/29/14 0720 Natural Gasoline High High O2 Restarted left fuel gas in manual
10/30/14 1655 Crude Oil High High O2 spot 2 Bled transmitter
11/20/14 1441 Natural Gasoline High High O2 Restarted valve 1111. Would not reopen, reboot panel.
12/02/14 0557 Natural Gasoline High High Stack Temp Restarted and lowered fuel gas.
12/02/14 0655 Natural Gasoline High High Stack Temp Restarted stack temp was only showing 1875.
12/10/14 1850 Natural Gasoline High High Stack Temp Restarted twice before we kept it going.
12/10/14 1935 Natural Gasoline High High Stack Temp Want restart // Called Tech out
10/10/14 1750 Natural Gasoline Burner 4 High High Temp. Flare Gas still running. Showed off at panel. Re-started Flare and resumed loading
12/19/14 0600 Natural Gasoline Vapor Valve Failure Shutdown System. Restart Panel Power
01/15/15 1127 Natural Gasoline Vapor Valve Failure Used pipe wrench to open vapor valve (Tommy)
02/10/15 1230 Natural Gasoline Vapor Filter Plugged Changed Filter
02/17/15 1900 Natural Gasoline Inoperative Buzzer Alarm New Buzzer Alarm
02/17/15 1917 Natural Gasoline Flow control vavle inoperable I & E Tech onway to fix
02/18/15 0130 Natural Gasoline Liquid Block Valve Failure Plugged Air Leak in back of Panel
04/15/15 0850 Natural Gasoline Burner 2 High High Temp. Entered Flare Stack to Inspect/Clean Burner Tip/Thermacouple.
06/05/15 1330 Natural Gasoline Flare Pilot Failure Burner Tips Messed up. Ran both Flares.
06/30/15 1548 Natural Gasoline 1201 Pilot Failure Working on Flare 1301. Shut down Flare 1201.
06/30/15 1559 Natural Gasoline High High O2 Shutdown Flare Valve Shut
07/18/15 0915 Natural Gasoline AIT 1119A Low Flow Replaced Solenoid Switch
07/21/15 2030 Natural Gasoline No Flow 1119A After Multiple Shutdowns, Moved Barge to Spot 3
10/16/15 1400 Natural Gasoline 1301 Pilot Failure I & E Fixed Problem
05/16/16 0410 Natural Gasoline 1302 Flare Failure/O2 Failure I & E Fixed Problem
02/15/17 0600 Natural Gasoline Vapor Valve Tail Changed Filter
11/18/20 1115 Natural Gasoline Drain vapor hose going to flare under catwalk Drained Hose
11/30/20 1500 Natural Gasoline Drain Vapor Hose Drained Hose
12/24/20 1800 Natural Gasoline Plugged Vapor Hose Drained Hose
01/18/21 1200 Natural Gasoline Hi Hi Pressure Flared Down Barge